Skip to main content

A fire in the hydrotreatment oven of a refinery (103)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

A fire in the hydrotreatment oven of a refinery

An explosion, followed by a fire, happened in an oven belonging to the hydro-treatment unit. Following a shutdown, the tube, containing only gaseous products and hydrogen, had been affected by instable flows. In presence of a flows lower than nominal, the tube temperature raised up to its mechanical resistance limit. Under internal pressure, it failed with a longitudinal crack of ca. 750 mm The unit was shut down and the fire extinguished by itself.
Event Date
December 7, 2005
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the failure of a tube of the oven due to overheating. The the destabilisation of the operative conditions was due to shortcoming in the capacity to control the operative parameters, also due to lack of effective diagnostics by means of measuring gauges.
Facility Information
Application Type
Application
hydrotreatment
Specific Application Supply Chain Stage
Components Involved
Hydrotreatment unit
Storage/Process Medium
Location Type
Location description
It is probable that the oven affected by the explosion was a heat exchanger used to pre-heat hydrogen and other process gases before entering he hydro-treatment reactor.
Operational Condition
Pre-event Summary
The oven used for hydrotreatment of complex oils had been shut down 3 hours before.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

As a maintenance was planned in January 2006, the unit will not restart before this date.

Event Nature
Emergency Action
The Internal Operation Plan was launched. The unit was secured by using extinguishing means, isolatiing it, depressurising it and placing it under nitrogen. The integrity of all equipment surrounding the oven was checked.
Release Type
Release Substance
H2 (mainly)
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event no. 52706 of the French database ARIA (accessed December 2020)