Skip to main content

Fire on a hydrogenation reactor of a refinery (648)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on a hydrogenation reactor of a refinery

A weld on a 1 inch diameter instrument tapping from a Octafiner reactor overhead line fractured, resulting in a small but intense fire, lasting about 50 minutes until the unit was nitrogen purged. The fire was always under control and the fire fighting effort was directed solely to cooling the surrounding metal with fire steam lances. Plant Inspection reported that the failure was due to hydrogen embrittlement of the heat affected zone of the tapping and probably resulted from improper or no stress relieving of the connection during construction.
Event Date
February 2, 1973
Record Quality Indicator
Region / Country
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the failure of a weld on an instrument line of the reactor. The fracture was due to hydrogen embrittlement, probably worsened by the presence of non-design stress probably due to an inadequate heat treatment for relieving welding stress. The ROOT CAUSE could then be attributed to manufacturing shortcoming, possibly together with choice of non-optimal materials. Nothing is known on the inspection procedures which could identify degradation in its early stage.
Facility Information
Application Type
Application
Hydroisomerisation process
Specific Application Supply Chain Stage
Components Involved
octafining reactor pipe, weld
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE PROCESS The Octafiner process is catalytic hydrogenation process. It is a patented technology aiming at upgrading heavy oils and distillates into lighter, higher-value products. This process is used to remove sulfur, nitrogen, and metals, and to saturate aromatics, which improves the quality of the product.
Operational Condition
Pre-event Summary
PRCOESS
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Lessons Learned
The emergency measures taken were effective in containing the emergency and avoiding escalation. Probably the fact that the fire was small helped in not affecting surrounding component. The measure which solved the emergency was the purging by nitrogen, which stopped the fire.
Event Nature
Emergency Action
The fire was always under control and the fire fighting effort was directed solely to cooling the surrounding metal with fire steam lances. The fire stoppedwhen the reactor was nitrogen-purged (which implies that it was shutdown first).
Release Type
Release Substance
unknown
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description extracted from the UK database ICHEME in PDF ICHEME database is no longer available for purchase, but data can be download as PDF for free. https://www. icheme. org/knowledge/safety-centre/resources/accident-data/ (accessed October 2020)