Fire in the hydrogen storage and supply system of a nuclear power plant
A hydrogen skid was placed into service in a nuclear power plant, outside the controlled area. This skid, like seven others, was located in a gas cylinder storage facility. It was supplied by several hydrogen cylinders at a pressure of 200 bar. As its pressure was rising, a manifold on the skid was blown off, causing the hydrogen to leak and ignite. The flaming jet measured 40 cm and continued as the system was open. Surprised by the incident, an employee fell and slightly injured his arm. The site’s internal emergency plan was initiated. The storage facility was located just 20 m from a 400 kV high-voltage power line. The use of hydraulic means was therefore impossible. Firefighters were able to close the hydrogen supply valve, which stopped the leak. The two skids impacted by the fire were removed from service. The analysis of the accident showed that the manifold was loose and that its threads were worn. Mechanical friction during the expulsion had released enough energy to ignite the hydrogen. The operator conducted electrical and mechanical inspections of all the site’s gas storage facilities. 60% of the manifoldswas found with tightening defects.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE is the failure of a loose manifold on a skid causing the hydrogen to leak and ignite. Following the incident, an inspection found that a lack of tightening on 60% of the manifolds. Therefore the ROOT CAUSE could be identified in a lack of a an effective procedure for the installation and inspections of the skids high presure components.
