Fire in a hydrogen refuelling station (1106)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in a hydrogen refuelling station

A hydrogen leak in the hydrogen compressor unit of a filling station ignited causing the shut down of the whole station. The loss of containment was due the failure of a tie rod (diameter ~64mm) , which had the structural function holding together all compressor parts. The failure caused an hydrogen leak at high pressure. A large amount of hydrogen was released from the compressor to the compressor container within a short time, ignited followed by a deflagration or explosion inside the container. A part of the tie rod was shot to the side wall of the container. One door of the container was detached and was stopped by the fence in 10 m distance. Firgefighters were on site within 10 min and got quickly the fire under control . No injury, considerable material damage, limited to two containers.

Event Date
June 25, 2024
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

INITIATING CAUSE: Mechanical failure of a structural component of the hydrogen compressor. ROOT CAUSE : The metallographic investigation revealed that the tie rod failed by inter-granular brittle fracture, suggesting a wrong thermal treatment of the rod material.

Facility Information
Application Type
Application
HRS
Specific Application Supply Chain Stage
Components Involved

compressor

Storage/Process Medium
Storage/Process Quantity
500
Actual Pressure
70
Design Pressure
70
Location Type
Location description

DESCRIPTION OF THE REFUELLING STATION The fuelling station delivers LNG and hydrogen. The hydrogen part is newer. It has two dispensers to provide 350 and 700 bar hydrogen serving private cars, buses, special vehicles to heavy trucks. Its capacity is 500 kilograms per day, able to refuel 10 to 20 commercial vehicles.

Operational Condition
Pre-event Summary

The hydrogen refuelling station had been opened a week before the incident. A CGH2 tube trailer was on site, probably to deliver hydrogen to the HRS>

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Damage unknown. From the pictures provided by the sources, the compressor housing and its contents appears destroyed. The refuelling station operator plans to resume supplying vehicles with hydrogen in the autumn. The compressor manufacturer checked the three other systems installed in other hydrogen refuelling stations.

Lessons Learned

The safety measures in place worked as intended. A preliminary conclusion from this and similar events is that the individual technologies belonging to the hydrogen supply chain are still not yet fully mature. Possible causes are (i) the limited field experience gained so far, and (ii) the small amount of components produced, which hinders fully fledged quality insurance.

Event Nature
Emergency Action

The fire brigade established a safety perimeter, closed the valve feeding the compressor. By using several permanent extinguishers they kept cooled the components and a trailer present on site. The fire was quickly under control. https://www. feuerwehr-neusaess. de/einsatzbericht/brand-wasserstoff-tankstelle/

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

The investigation report by TÜV Süd is not publicly available. A summary was shared by NOW in a presentation of 8 Octobr 2024

PV-Magazine news of 07 July 2024: https://www. pv-magazine. de/2024/07/11/beschaedigter-kompressor-verursacht-brand-in-wasserstoff-tankstelle/ (accessed July 2024)

JRC discussion based on own collection of information