Fire in a hydrogen refuelling station
A hydrogen leak in the hydrogen compressor unit of a filling station ignited causing the shut down of the whole station. The loss of containment was due the failure of a tie rod (diameter ~64mm) , which had the structural function holding together all compressor parts. The failure caused an hydrogen leak at high pressure. A large amount of hydrogen was released from the compressor to the compressor container within a short time, ignited followed by a deflagration or explosion inside the container. A part of the tie rod was shot to the side wall of the container. One door of the container was detached and was stopped by the fence in 10 m distance. Firgefighters were on site within 10 min and got quickly the fire under control . No injury, considerable material damage, limited to two containers.

INITIATING CAUSE: Mechanical failure of a structural component of the hydrogen compressor. ROOT CAUSE : The metallographic investigation revealed that the tie rod failed by inter-granular brittle fracture, suggesting a wrong thermal treatment of the rod material.