Fire on a hydrogen cylinders rack
A release of hydrogen occurred during the filling of a 28 bottles rack. A worker decided to move the rack from one station to another, due to works ongoing nearby. This movement, even though the hose had remained connected to the rack, caused the bracket to break and the compressed hydrogen to leak. The jet was directed against the barrel of cylinders. Hydrogen sensors triggered the shutdown of the installation, including the closure of the feeding valve. The worker detached the flexible and started moving the rack towards the water supply. During its route around the building, the leak ignited. He secured the rack on the ground and gave the alarm.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause of the hydrogen release was the pulling away of the rack during filling. According to the ARIA report (see references), the formal accident investigation found out that the configuration of the filling station did not provide a clear view of the filling hose connection (see lesson learned for corrective actions).