Fire from a filling hose
A hydrogen leak caused a fireball in in an industrial gas processing and conditioning plant. The leakage occurred at the end of a hose in the packaging station, consisting in filling of tanks placed on trailers ready to be tracked away. The sound typical of an explosion was heard. The site's hydrogen supply was automatically cut off thanks to safety devices. Packaging was suspended while the source of the incident was determined. The operator had just disconnected the hose used to fill a semi-trailer. He had done so to replace a check valve that was vibrating noisily during filling. The hydrogen supply was off, the automation had been switched to manual mode, and the hose had been purged and disconnected. Nevertheless, pressurised hydrogen entered the disconnected hose, causing the leak. The report used as a source for this event explains the presence of hydrogen in the hose by the fact that the hose's anti-whip cable remained attached. This however does not make any sense, because an anti-whip cable is not a high-pressure connection and does not carry any gas. The operator in charge of filling was unharmed but shocked, and a psychological support unit was set up for the employees.

The INITIATING CAUSE was the accidental release of hydrogen from a hose which should have been disconnected and emptied. The explanation provided by the sources used for this event is flawed and cannot be used to extract a ROOT CAUSE, which could be only tentatively appointed to a human error or to unclear procedures.