Fire in a in a fertiliser manufacturing plant
The incident took place on the reforming furnace unit of the plant. Around 23:30 pm, during a normal inspection tour, an operator detected a fire on a section of a steam line. The operator immediately informed the control room. The unit was reduced in speed, with process parameters monitored to ensure that the situation did not worsen. Steam hoses were used in the direction of the flame and the identified hot spots. The next morning at around 6:00 am, the unit was progressively shut down and the fire extinguished. The reforming furnace unit consisted of 198 tubes containing a catalyst. Each furnace contained 11 headers on which 18 reforming tubes were welded. Each header was enclosed in a box and fed the transfer line to the secondary reforming. The fire occurred in one of the boxes containing the header and had no impact on the surrounding area or equipment. An investigation of the causes, carried out after the removal of the affected vessel, showed a leak on a gasket, caused by a weakened flange. The gasket was intact, no trace of leakage was detected.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE is the leakage of gas from a flange, the thightness of which had partially loosened.