Fire in the desulphurisation unit of a refinery
The accident occurred in the de-sulphurisation unit, and specifically on a pipeline at 50 bar, for the recycling of the hydrogen (containing hydrogen sulphide impurities). The pipe failed due to corrosion and the released hydrogen ignited. The unit was containing 4000 kg of hydrogen, but it is not known if all of it was released. The unit was stopped, de-pressurised and put under nitrogen. Following the accidents, all other pipeline were controlled looking for anomalies.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the failure of a hydrogen pipe due to corrosion. The accident investigation discovered that the part of the 100 mm diameter pipe which failed had a residual thickness of 2 instead of the nominal 6. 3 mm. The ARIA report (see references) does not mention any root cause, but judging by the deep corrosion, a lack of adequate inspection/maintenance can be postulated.