Fire in the desulphurisation unit of a refinery (114)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire in the desulphurisation unit of a refinery

The accident occurred in the de-sulphurisation unit, and specifically on a pipeline at 50 bar, for the recycling of the hydrogen (containing hydrogen sulphide impurities). The pipe failed due to corrosion and the released hydrogen ignited. The unit was containing 4000 kg of hydrogen, but it is not known if all of it was released. The unit was stopped, de-pressurised and put under nitrogen. Following the accidents, all other pipeline were controlled looking for anomalies.
Event Date
October 20, 1995
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the failure of a hydrogen pipe due to corrosion. The accident investigation discovered that the part of the 100 mm diameter pipe which failed had a residual thickness of 2 instead of the nominal 6. 3 mm. The ARIA report (see references) does not mention any root cause, but judging by the deep corrosion, a lack of adequate inspection/maintenance can be postulated.
Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
hydrogen recycling pipeline
Storage/Process Medium
Storage/Process Quantity
4000
Actual Pressure
5
Design Pressure
5
Location Type
Operational Condition
Pre-event Summary
Due to inner corrosion of a 100mm (DIN 100) pipe the wall thickness was reduced from 6. 3 mm to 2 mm.
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

2000000

Property Loss (offsite)

1500

Post-event Summary

1 injury, no fatality. The injury was due to the fact that an employee who had just left the plant was startled by the bang of the explosion and suffered a sprained ligament in a sudden movement. The material damage were estimated around 3 millions et 3 000 DM (ZEMA reports 2 Meuros + offside loss due to vehicle pollution in the employee parking lot).

Lessons Learned
. Nevertheless, the fact that the pipe failed due to internal corrosion indicate a lack of fit-for-purpose inspection, able to detect material degradation on limited sections.
Event Nature
Emergency Action
Inside the plant, the air conditioning system in the control room was switched to recirculated air, the electrical power supply was switched off, the plant was depressurized, emptied and flushed with nitrogen. The plant fire brigade only used water as an extinguishing agent, mainly to cool plant components and to contain the fire. The extinguishing water was retained and only released for discharge after analysis. Outside the facility, the road to the plant was cordoned off by the police as a precautionary measure and air quality measurements were taken in the surrounding area.
Release Type
Release Substance
H2, H2S (impurities)
Hydrogen Release Concentration (%)
0.00
Release Amount (kg)
4000.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event from German database ZEMA https://www. infosis. uba. de/index. php/de/site/2854/zema/index/3170. html (accessed December 2024)

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/10347/ (accessed October 2020)