Fire on a compressor of a desulphurisation unit (761)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on a compressor of a desulphurisation unit

In a hydro-desulphurisation unit of a refinery, an operator which was performing a control tour heard noises and clicks on the hydrogen compressor and stopped it. The compressor was of a reciprocating compressor with 2 opposite cylinders and 1 stage, operating at 60 bar. When the compressor was stopped, the cylinder broke and released hydrogen-rich gas that ignited 15 to 20 seconds later. The suction separator tank was equipped with 2 level alarms, one of which was coupled with the safety emergency stop. Their good functioning had been tested and should have excluded the massive arrival of liquid. No precursors could be found in the control room. Oil was found in the discharge manifold and a presence of greasy deposits on the outer face of the piston and on the bottom of the cylinder. In addition, the valves were heavily fouled and the suction filter partially clogged with deposits. Non-compliance with procedures was one of the components causing the accident.

Event Date
June 1, 1977
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was clogging of the itneral piping due to deposits. ROOT CAUSE was the lack of effective maintenance and inspection. Non-compliance with procedures was one of the components causing the accident.

Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved

hydrogen compressor

Actual Pressure
6
Design Pressure
6
Location Type
Operational Condition
Pre-event Summary

an operator heard noises and clicks on the hydrogen compressor and stopped it.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Oil was found in the discharge manifold and a presence of greasy deposits on the outer face of the piston and on the bottom of the cylinder. In addition, the valves were heavily fouled and the suction filter partially clogged with deposits.

Event Nature
Emergency Action

The operator stopped the compressor. The suction separator tank was equipped with 2 level alarms, one of which was coupled with emergency stop. However, this did not worked.

Release Type
Release Substance
H2, hydrocarbons
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

ARIA data base event no. 23138