Fire at a chlorine electrolyser plant
Chlorine was released in the liquefaction unit of a chlorine electrolysis plant, due to the rupture of a pipe. During the re-start phase of an electrolysis workshop in a chemical plant, chlorine (Cl2) gas leaked from a pipeline in a confined chlorine liquefaction unit, specifically at the pipeline carrying residual chlorine from the gas/liquid separator to a liquid bleach manufacturing plant. The leak took place when few tens of cm of this pipeline failed, due to the combustion of the pipeline steel by chlorine, which in turn was caused by the presence of hydrogen in the pipeline due to lack of monitoring. According to the rules, hydrogen concentration in the residual chlorine must remain below the 4. 6 %vol value (the hydrogen low explosion limit, LEL). It is manually controlled by the rate of evaporation of chlorine in the gas/liquid separator and monitored through analysis. During the accident, the technician failed to reduce the increasing hydrogen concentration in the pipeline that reached 6. 7%, crossing the LEL. To bring down the concentration, the evaporation rate of chlorine was increased causing thus a rise in the residual chlorine flow rate. This probably provided the low energy needed to start combustion. The flame stabilised near a valve and a flow meter and caused the combustion of iron / chlorine when the temperature reached 130 °C.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause of the accident was the ignition of the chlorine in the pipeline due to a hydrogen content above the allowed maximum. Nothing is said on the reason of this hydrogen increase. An intermediate cause was the attempt to reduce the probability of hydrogen-chorine combustion by increasing the chlorine flow. is present within residual chlorine in the pipe. The concentration is monitored and should not go over LIE (4. 6%). During the incident, this concentration went to 6. 7% without reaction of the operator. To lower this value, the evaporation rate of chlorine is increased by increasing the flow which probably gave the small energy needed to ignite the H2/Cl2 melt. This ignition results in the burning of the steel pipe : tens centimetres of pipe disappeared resulting in the detected Cl2 leak.