Fire at a chlorine electrolyser
Two successive fires broke out in an interval of few minutes in four cells in the electrolysis room of a chlorine production plant. The technicians brought the fire under control using the fire-fighting equipment located nearby. In both cases presence of hydrogen, ignited by a short circuit spark, was responsible for the two accidents. Case (1): the hydrogen leaked when a rubber-plastic pipe was manually disconnected from a hydrogen trap. Despite the fact that that this operation is covered by a specific procedure, it was performed when hydrogen quality was not good enough to be collected. Case (2): the hydrogen leaked when a sleeve failed locally by corrosion.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The two sub-events have the same INITATING CAUSE, a hydrogen fires during operation. The two fires have different two ROOT CAUSES. In case (1) was a wrong operation (in presence of a formal procedure). In case (2) it was probably a design or inspection shortcoming (corrosion). The following investigation identified FACTORS related to design The IGNITION SOURCE of the released hydrogen was an electrical spark caused by a short-circuit. Different potential causes of the short-circuit were identified: - the compatibility of insulating material has not been checked - lack of wet-proofing between anode and cathode - not enough distance between anode and hydrogen pipe due to a modification of the connection and a miss-alignment of the cells