Fire on a CGH2 trailer during filling
Near the end of the process of filling a gaseous hydrogen tube trailer at a liquid hydrogen trans-filling station, a safety pressure-relief device (PRD) rupture disc on one of the tube trailer’s burst and vented hydrogen gas. The PRD vent tube directed gas to the top of the trailer where the hydrogen vented and ignited, blowing a flame straight up in the air. The operator filling the tube trailer heard a loud explosive sound from the sudden release of hydrogen gas and saw flames immediately. The operator closed the main fill valve on the tube trailer, stopping the hydrogen fill; however, the ten cylinders on the tube trailer were almost full (2500 psig/173 bar). The facility deluge system was turned on and the emergency responders sprayed the adjacent trailers to prevent escalation. The emergency crews closed the 10 individual tube fill isolation valves located at the rear of the tube trailer and this extinguished the fire. There was no property damage from this event. The PRD rupture disc designed for 3500 psig (241 bar) failed at about 1000 psig (69 bar) below rated pressure.

The INITIATING CAUSE was the premature failing of the burst disc. Post-incident examination of the PRD rupture discs lot by the manufacturer found that all of the lot conformed to specification. According to H2TOOLS report, the ROOT CAUSE was an unexected premature failure of the burst disk .