Skip to main content

Fire from a CGH2 cylinder (592)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire from a CGH2 cylinder

This incident occurred during the delivery of a hydrogen gas container to a customer site. When a worker turned the protective cap of the container, the valve handle turned together with the container, causing hydrogen gas to leak and ignite, resulting in the worker being burned.

Event Date
August 29, 1997
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the accidental (erroneous) opening of the release valve. The KHK report attributes the ROOT CAUSE to a wrong operation (bad handling). However, this incident should not be made possible by passive safeguards. The fact that it was possible reveal a mistake in the design of the equipment, which did not considered a possible wrong operation.

Facility Information
Application
CGH2 cylinders
Specific Application Supply Chain Stage
Components Involved

valve, cylinder

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Post-event Summary

The worker of the delviery company received burns

Lessons Learned

This is a case of release and fire attributed to a wrong operation. However, passive safeguards should made impossible the activation of the release valve while opening the protective cup of a high-pressure cylinder. This is for example obtained by blocking the wheel of the valve by means of a steel cable and a seal.

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): https://www. khk. or. jp/public_information/incident_investigation/hpg_incident/incident_db. html (accessed May 2025)

The first entry in HIAD was coming from RISCAD, which is now closed.