Fire on an alkaline electrolyser (1065)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on an alkaline electrolyser

A fire broke out on the insulating plastic elements of an alkaline electrolyser in a unit of a chemical plant. The shift saw the smoke from the control room. The first action was to drain the potash into a tank provided for this purpose and to shut down the electrolyser. The on-call electrician interrupted the electricity. The safety technician brought the fire under control in less than 10 minutes using CO2 extinguishers. After approximately six hours, the unit is restarted.
Event Date
September 10, 2022
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE of the event was potash leak on the electrolyser block that induced an electric arc between the electric block and the bus bar. This ignition caused a rise in temperature followed by the outbreak of fire.
Facility Information
Application Type
Application
water electrolysis
Specific Application Supply Chain Stage
Components Involved
Alkaline electrolyser
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

0

Property Loss (offsite)

0

Event Nature
Emergency Action
The following steps were taken: • The potash was drained into a tank provided for this purpose and to shut down the electrolyser. • The on-call electrician interrupted the electricity. • A no-go area is defined with ribbons and the metallic curtain are opened to provide natural ventilation. • The technician controls the electrolyser using a thermal camera. • The safety technician brought the fire under control in less than 10 minutes using CO2 extinguishers. • After approximately six hours, the unit is restarted.
Release Type
Release Substance
KOH (solution)
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

ARIA event https://www. aria. developpement-durable. gouv. fr/accident/59900/