Failure of a high pressure synthesis feed pipe in an ammonia plant.
The failure of a high pressure hydrogen-based synthetic gas feed line to the ammonia converter produced a sudden explosion followed by a severe fire. One of the operators was fatally injured. The failure of the feed line was characterized by a sudden rupture. There was no leakage prior to rupture. Portions of the piping shattered in a brittle fracture, which was produced due to a severe hydrogen attack. Extensive blisters were observed on the inside surface which failed. The initial crack probably originated at one of two small nozzles provided for temperature measurements. These small nozzles acted as stress raisers.
Event Date
December 9, 1984
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was failure of a high pressure synthesis pipe due to internal hydrogen attack, which induced steel decarbonisation and brittle fracture. Probably the possibility of the hydrogen attack was not taken into consideration in the design and the maintenance phases.