Explosion when venting hydrogen
After completion of a process using hydrogen an explosion occurred in the vicinity of the vent stack. Cold hydrogen gas was being vented into the atmosphere for about 45 minutes. The weather was unusually calm and the gas probably accumulated around the vent stack area and ignited. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the formation of a hydrogen-air flammable mixture at the exit of the vent stack, due to lack of wind able to disperse the hydrogen. The fact that the safety design of the vent was based on expectation of enough wind, suggests a ROOT CAUSE related to its design.