Explosion of several hydrogen bottles
Hydrogen gas cylinders exploded at the same time in three industrial locations, when the opening valve was opened. The overpressure generated by the explosion caused the walls of the hydrogen cylinder storage room to collapse, six workers were killed. The hydrogen cylinders used by the three companies were filled by the same company. The investigation found that a large amount of air was mixed with hydrogen in many of the delivered cylinders, the air accounting for 50% of the total volume. When the operator opened the cylinder valve, the friction between the air flow and the bottle valve generated static electricity, which directly detonated the cylinder. The company delivering the cylinders fills more than 1,000 cylinders in the same batch. These 20 MPa compressed hydrogen cylinders are filled from a hydrogen storage tank using two buffers tanks and two hydrogen compressors in parallel. According to the scientific article quoted in the references, the night before the accident, the company has experienced a reduction of the power supply. Answering to this, the operator ordered to close both the two valves delivering hydrogen to the compressors, after confirming that the compressors had stopped working. When the hydrogen compressor restarted, one of the valves was open, while the other was still close. This caused the development of vacuum in front of one of the hydrogen compressor, which continuously increased with time. After the pressure difference reached a certain level, the explosion-proof film in the buffer tank cracked and a large amount of air was sucked by the compressor and pumped into the hydrogen cylinders, mixed with hydrogen. A contributing cause was the rain of the night before, which dampened the explosion-proof membrane in the buffer tank.
Event Date
July 23, 2004
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the explosion of the tanks due to presence of a hydrogen-air mixture inside them. Instead of hydrogen, the tanks had been filed and delivered by the gas producer containing th ewrond (explosive) composition. The ROOT CAUSE is related in first instance to an operative mistake, related to an erroneous manual control of the valves controlling the gas flow. However, several factors enabled the occurrence of this event: a bad design, a lack of automatic process system, a lack of gas composition control during the process and before delivery. Additional environmental and technical causes contributed to it. Finally, it is evident that that specific accidental scenario was not considered in during the designing phase.