Skip to main content

Explosion in a methanol synthesis unit (770)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a methanol synthesis unit

The accident happened in a low pressure methanol plant, commissioned in summer 1971 . A 6 in. pipe, below the methanol synthesis gas compressor inter-stage relief valve, failed releasing hydrogen-rich synthesis gas into the methanol area. The pipe failed at the pipe-flange junction. Syngas was ignited by an unknown ignition source and the resultant fire burned 10-20 minutes above the synthesis gas compressor. No damages to personnel are reported, even though windows were broken within a distance of 270 m, due to the explosion. It is not known whether the pipe failure was due to fatigue or to a sudden overload. According to Lloyd (see references), a weld neck flange should have been used instead of lap-joint flange; the former shows higher fatigue life (approximately ten times) under cyclic operation.
Event Date
January 1, 1983
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
It is not known whether the pipe failure was due to fatigue or to a sudden overload.
Facility Information
Application Type
Application
Methanol production
Specific Application Supply Chain Stage
Components Involved
pipe of a methanol synthesis gas compressor
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE PROCESS The Benfield process, uses a solution of potassium carbonate solution (K2CO3) as an absorbent to eliminate CO2 from a gas mixture. The gas to be cleaned is passed at high pressure (e. g. , 2 MPa) countercurrently through the K2CO3 -solution in the absorber. This becomes enriched with CO2 and partially reacts to form potassium bicarbonate (KHCO3).
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Lessons Learned
The recommendation of the author of the article reporting the incident was to use weld-neck flanges instead of lap-joint or stub-end flanges. The reason is the much longer lifetime under fatigue conditions of the former than the latter. A weld-neck flange is a flange which has a pipe-formed part which is welded head-to-head to the pipe. A lap-joint or stub-end flange use a stub-end which has to be welded on one side to the flange and to the pipe to the other side.
Event Nature
Release Type
Release Substance
syngas
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

W. D. Lloyd, Methanol synthesis gas explosion. Weld-necks flanges should be used for cyclic operation, since their fatigue life is ten times that of a lap-joint flange and stub-end combination, Process Safety Progress 2 (1983) 120-121 https://doi. org/10. 1002/prsb. 720020212