Explosion in a methanol synthesis unit
The accident happened in a low pressure methanol plant, commissioned in summer 1971 . A 6 in. pipe, below the methanol synthesis gas compressor inter-stage relief valve, failed releasing hydrogen-rich synthesis gas into the methanol area. The pipe failed at the pipe-flange junction. Syngas was ignited by an unknown ignition source and the resultant fire burned 10-20 minutes above the synthesis gas compressor. No damages to personnel are reported, even though windows were broken within a distance of 270 m, due to the explosion. It is not known whether the pipe failure was due to fatigue or to a sudden overload. According to Lloyd (see references), a weld neck flange should have been used instead of lap-joint flange; the former shows higher fatigue life (approximately ten times) under cyclic operation.
Event Date
January 1, 1983
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
It is not known whether the pipe failure was due to fatigue or to a sudden overload.