Explosion in a hydrogenation unit of a refinery

The event occurred at a hydrogen processing unit of the refinery. A mixture of hydrocarbon and hydrogen leaked ad the 90-debrees-elbow of a carbon steel pipe. The mixture formed a cloud which exploded. The investigation concluded that the failure of the line was the result of the thinning of the carbon steel elbow due to long-term erosion/corrosion. The explosion was followed by fires which caused extensive damage to the hydrocracker, hydro-desulphurisation, and hydrogen processing units. The explosion is classified by one of the source (Oral et al. ) as a Vapour Cloud Explosion (VPE).
Event Date
October 8, 1992
Record Quality Indicator
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause was the failure of a pipe due corrosion. Inspection was possibly not able to detect the damage, but it is not known if this was due to limitation of the non-destructive equipment , to the absence of the correct inspection schedule or incorrect assessment of the risk and consequences. ICHEME/MHIDS reproted a wrong dimension of the failed part, which suggest A ROOT CAUSE related to installation errors, wit ha contribution from an inadequate inspection.
Facility Information
Application Type
Application
hydrogenation unit
Specific Application Supply Chain Stage
Components Involved
Pipe and valve
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
16
Currency
Property Loss (onsite)

78800000

Property Loss (offsite)

550000

Post-event Summary

The fire was visible from 32 km away. People in a 5 sq. km area were evacuate. Material damage is significant ($ 78. 3 million). Los Angeles Times reproted 14 light injuries, Rigas&Amyotte 16.

Event Nature
Emergency Action
People in a 5 sq. km area were evacuated. The fire-fighting effort was coordinated by the refinery emergency response team, with the city and County fire departments using the joint incident command system. The refinery emergency response team placed booms to stop oily water run-off generated by the firefighting effort from reaching the city harbour. The fire was finally extinguished after three days.
Release Type
Release Substance
H2 hydrocarbon
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

MARSH report, 100 largest losses in the hydrocarbon industry, 27th edition 2022 https://www. marsh. com/cz/en/industries/energy-and-power/insights/100-largest-losses. html (accessed January 2024)

ARIA database event 11282 https://www. aria. developpement-durable. gouv. fr/accident/11282/ (accesed November 2025)

Event 5815 of the UK database ICHEME/MHIDAS The database is no longer available , but data can be download as PDF . https://www. icheme. org/knowledge/safety-centre/resources/accident-data/ (accessed October 2020)

Los Angeles news https://www. latimes. com/archives/la-xpm-1992-10-09-mn-724-story. html (accwssed November 2025)

Rigas F. , Amyotte P. , Hydrogen safety, Green chemistry and chemical engineering, CRC Press, Taylor & Frances Group; 2012. ISBN-13: 978-1439862315