Explosion in a hydrogenation unit of a refinery
The event occurred at a hydrogen processing unit of the refinery. A mixture of hydrocarbon and hydrogen leaked ad the 90-debrees-elbow of a carbon steel pipe. The mixture formed a cloud which exploded. The investigation concluded that the failure of the line was the result of the thinning of the carbon steel elbow due to long-term erosion/corrosion. The explosion was followed by fires which caused extensive damage to the hydrocracker, hydro-desulphurisation, and hydrogen processing units. The explosion is classified by one of the source (Oral et al. ) as a Vapour Cloud Explosion (VPE).
Event Date
October 8, 1992
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause was the failure of a pipe due corrosion. Inspection was possibly not able to detect the damage, but it is not known if this was due to limitation of the non-destructive equipment , to the absence of the correct inspection schedule or incorrect assessment of the risk and consequences. ICHEME/MHIDS reproted a wrong dimension of the failed part, which suggest A ROOT CAUSE related to installation errors, wit ha contribution from an inadequate inspection.