Explosion at the hydrogenation tower of a refinery
The explosion occurred inside the lower hydrogenation tower of a hydrogen peroxide unit, damaging the distribution tray inside the tower. it caused 4 fatalities, 2 injuries and considerabledamage to the installation. The company was replacing the catalyst, becasue of the decresed catalyst efficiency in the fixed bed of the lower hydrogenation tower. This is the DETAILED SEQUENCE: • January 14: the old catalysts was unload of the lower and middle towers; • February 8: The middle tower was refilled, the upper and lower towers were not refilled; • March 13: Feeding and start-up was initiated, but only partial flow of the fixed bed in the middle tower and an uneven distribution of working fluid were noted; • March 16: The leader of the hydrogen peroxide plant replaced the nitrogen inlet pipeline of the middle tower with a pure hydrogen inlet pipeline, but the problems of partial flow of the fixed bed in the middle tower and uneven distribution of working fluid were not resolved; • March 17: The technician of the new catalyst supplier suggested adding a few more sieve trays to the middle tower distribution tray; • March 18: from 8:00 am to 9:00 am, the leaders agreed to measure the upper part of the lower tower in order to install the middle tower working fluid inlet facility. At 8:40, workshop director and other 5 employees went to the third-floor platform of the device to check the measurement situation. At 9:26, two employees went to the platform on the fifth floor. At 9:32, one employee entered the lower tower at the same time. At 9:47:40, an explosion occurred inside the lower tower.
Event Date
March 18, 2015
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the hydrogen inlet line shut-off valve leakage: hydrogen gas leaked internally into the tower and mixed with the air entering from the upper manhole, creating an explosive atmosphere and igniting . A CONTRIBUTING CAUSE was the fact that the personnel of the enterprise did not take effective isolation measures and entered the lower tower of the hydrogenation tower to work. ROOT CAUSE was a lack of risk management, of effective maintenance procedures, of risk assessment, of preventive and mitigation measures. A possible ignition source was sparks from electrostatic frictions produced by the use of non-explosion-proof tools. Operators were not carrying explosion-proof steel socket spanners when accessed the tower.