Explosion at a hydrogen storage of a research facility (525)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion at a hydrogen storage of a research facility

An explosion took place at a research facility of a university, due to an accidental release of hydrogen. Hydrogen gas was used in research reactors to deposit amorphous silicon thin films. The release occurred during the replacement of a hydrogen cylinder stored in a gas cabinet. The cabinet was used to store and supply hydrogen and other hazardous gases to an enclosed reactor in an adjacent room. During the replacement of the compressed hydrogen cylinder, a quantity of hydrogen at a pressure of more than 1100 psi (75 bar) was accidentally released through a line used for vacuum purging. The explosion occurred when a vacuum bellows burst releasing the gas into the reactor enclosure. The Plexiglas walls of the reactor enclosure blew outward causing extensive damage to the laboratory. No one was in the room at the time of the incident, and no one was injured.
Event Date
September 1, 1992
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the erroneous release of high-pressure hydrogen into a vacuum system not rated for this amount of pressure. This was triggered by the error of an operator who opened a valve in the wrong sequence The ROOT CAUSE was related to the absence of a formal policy for the systematic oversight of gas handling and safety systems, together with a poor ga handling design.
Facility Information
Application Type
Application
phtovoltaic laboratory
Specific Application Supply Chain Stage
Components Involved

valve

Storage/Process Medium
Actual Pressure
7
Design Pressure
0
Location Type
Operational Condition
Pre-event Summary
The explosion occurred during the replacement of a hydrogen cylinder which was stored in a ventilated gas cabinet equipped with sprinklers.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (offsite)

0

Post-event Summary

The Plexiglas walls of the reactor enclosure blew outward causing extensive damage to the laboratory. No one was in the room at the time of the incident and no one was injured.

Lessons Learned
According to the investigation report, the incident was caused by the absence of a formal and regular review of the administrative, engineering and personnel programs associated with the compressed gas systems. Usually, a root cause is accompanied by contributing factors. These are as causal elements which did not necessarily directly result in the incident, but presented conditions in which the incident could occur. In this incident, the following contributing could be identified: (1) The human error at the start of the sequence of events. (2) A non-optimal design of the gas handling system, which, for example, was missing an excess flow valve and was not equipped with measures preventing mis-operations. (3) The absence of a written procedure or checklists for purging, cylinder changing, startup or shutdown of gas system or reactor. (4) A lack of formal training and testing programs for gas system operators.
Event Nature
Emergency Action
Unknown, probably none.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Moskowitz, P. , Buchanan, W. and Shafarman, W. , 1994. Lessons learned from a hydrogen explosion at a photovoltaic research facility. Proceedings of 1994 IEEE 1st World Conference on Photovoltaic Energy Conversion - WCPEC (A Joint Conference of PVSC, PVSEC and PSEC)