Explosion at a hydrogen storage of a research facility
An explosion took place at a research facility of a university, due to an accidental release of hydrogen. Hydrogen gas was used in research reactors to deposit amorphous silicon thin films. The release occurred during the replacement of a hydrogen cylinder stored in a gas cabinet. The cabinet was used to store and supply hydrogen and other hazardous gases to an enclosed reactor in an adjacent room. During the replacement of the compressed hydrogen cylinder, a quantity of hydrogen at a pressure of more than 1100 psi (75 bar) was accidentally released through a line used for vacuum purging. The explosion occurred when a vacuum bellows burst releasing the gas into the reactor enclosure. The Plexiglas walls of the reactor enclosure blew outward causing extensive damage to the laboratory. No one was in the room at the time of the incident, and no one was injured.
Event Date
September 1, 1992
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the erroneous release of high-pressure hydrogen into a vacuum system not rated for this amount of pressure. This was triggered by the error of an operator who opened a valve in the wrong sequence The ROOT CAUSE was related to the absence of a formal policy for the systematic oversight of gas handling and safety systems, together with a poor ga handling design.