Explosion at a hydrogen compressor of a sand oil company
The explosion occurred at a sand oil an explosion and affected the hydrogen compressor and its building, serving the hydrocracker unit. (1) More than two months before the incident, a large hydrogen release had already occurred due to the fail of the seal of the recycle compressor. This was the consequence of a series of events which had started with the trip of the pressure-swing absorption unit, causing the make-up compressor to shut down. When it was restarted, the recycle compressor seal system failed. Approximately 1500 kilograms of hydrogen were released into the building, which apparently did not ignited and did not cause any modification of the maintenance routine. (2) Ten days before the incident, the compressor to be overhauled was isolated from the rest of the facility, and the works to replace eight valves started. According to the investigation report, from days to days the maintenance team have been busy with various actions, up to the dismantling of some of the valves. During these days, the team compositions had changed, and unexperienced workers had joined. Also, the supervisors had been replaced by a less experienced one. (3) The explosion occurred on the day when all the valves were dismantled. According to one of the sources, the workers were not familiar with the site procedures, and the error triggering or enabling the incident was due to having isolated a single stage of a compressor rather than both stages .

The INITIATING/direct cause was the release of large quantity of hydrogen from the compressor being maintained, occurred when dismantling a valve. During the starting days of the maintenance, high temperature had been recorded on the compressor valves, the pressure-swing absorption unit has triggered, and the restart of the make-up compressor had caused a loss of integrity at the recycle compressor. The court charges to the company related to the failing to ensure the health and safety of the workers, and failing to ensure the compressor equipment was serviced in accordance with manufacturer's specifications. From this, it can be deduced that the root cause were due to Management shortcomings and Job Factors contribution. (i) The former is due to the lack of proper risk assessment, which did not consider the possibility of a large release of hydrogen, even if this had already occurred at the first day of the maintenance. It appears that the company was not (completely) understanding the complex phenomena occurring in the facility. (ii) The latter can be deduced by the fact that the workers had been asked to volunteer on the week end, and that the usual morning brief before starting works was not executed for a last days before the incident.