Explosion of hydrogen and gas oil with subsequent fire at a refinery

The incident occurred at a heat exchanger involving gas-product mixture. The source does not specify the process, with as main component a furnace, probably a hydrodesulphurisation reactor. Due to a leak in the pipe, the mixture was released and formed a vapour cloud. Following ignition, a fire developed at the leaking point. The plant fire brigade was alerted and laid a foam carpet over the entire area. The furnace system, the as circulation compressor and the injection pump were switched off in an emergency. The emergency expansion valve was opened and nitrogen was fed into the circuit. No injuries, only equipment damage.

Event Date
February 13, 1994
Record Quality Indicator
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments

A material failure was suspected to as INITIATING CAUSE of the leak. Nothing is known on the operative aspects of the event.

Facility Information
Application Type
Application
Unknown
Specific Application Supply Chain Stage
Components Involved

pipe, heat exchangeer

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

500000

Property Loss (offsite)

0

Post-event Summary

There were no personal injuries. The property damage due to partial destruction of equipment as a result of the fire amounted to 500,000 euros. There was no environmental damage.

Event Nature
Emergency Action

The plant fire brigade was alerted and laid a foam carpet over the entire area. As safety measures, the furnace system, the as circulation compressor and the injection pump were switched off in an emergency. The emergency expansion valve was opened and nitrogen was fed into the circuit. No intervention outside the plant was required.

Release Type
Release Substance
H2S 10 kg H2 100 kg Hydrocarbons 1200 kg