Explosion of a flammable mixture in a petrochemical plant
The incident occurred in a catalytic reforming unit. At 13:41, a leak occurred at the 90° elbow of a pressure pipe containing a mixture of hydrogen and naphtha. This pipe was located between the pre-hydrogenation heat exchanger and the pre-hydrogenation product tower heat exchanger. The flammable material leaking from the pipe burst into flames, and at 13:51 and 14:21 there were two more explosive combustions. Some of the nearby towers, pipelines and other equipment and facilities affected by the following high temperature flames continued to burn, with varying degrees of damage or rupture and leakage of combustible materials. The intensified combustions and fire triggered two subsequent deflagrations, 10 minutes and 40 minutes later respectively, after the first explosions.
Event Date
January 14, 2020
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause of the pipe rupture was corrosion. Due to corrosion, the wall thickness of the pressure pipe 90 ° elbow had become thinner and ruptured under an internal pressure of 0. 2 MPa with an opening of about 950mm × 620mm. The hydrogen gas mixture ejected to form an explosive mixture. The friction between the ejected gas and the pipeline generated electrostatic sparks, which triggered a fire. Regarding the root technical causes, the affected pipeline was continuously in an acidic environment. The company was not monitoring and analysing the acidic water in the pre-hydrogenation tank. The continued recycling of this acidic water led to increasing concentrations of H2S, HCl and NH3 and intensified the corrosion of the pipeline. A contributing cause was the temperature of the pipeline. The operating temperature of the affected pipe was supposed to be 150°C, and the design temperature was 170°C. However, the actual operating temperature of the pipeline at the time of the accident was about 180°C, and this accelerated the corrosion process. The investigation found also organisation causes in the failing of implementing preventive safety measures (see below at lesson learned).