Skip to main content

An explosion in an electrolyser for the production of chlorine (104)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

An explosion in an electrolyser for the production of chlorine

An explosion occurred in a electrolyser cell, blowing off the cell's vent cover and severing a low-pressure chlorine gas pipeline. , what caused a release of chlorine in the building, The event occurred when two operators were trying to improve the tightness of the diaphragm. They were only very lightly injured. A reaction between hydrogen and chlorine in the cell's headspace was responsible for the explosion. The migration of hydrogen towards the chlorine, producing an explosive mix, was due to excessive pressure in the cathodic compartment.
Event Date
September 5, 2005
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the diffusion of hydrogen into the chlorine half-cell, creating an explosive mixture. The post-incident analysis revealed a poor quality of the cell's diaphragm: it was part of a batch of diaphragms whose manufacture did not adhere to standard procedures (crosslinking temperature of 275°C instead of 355°C due to a furnace regulation failure) and which subsequently exhibited premature aging.
Facility Information
Application Type
Application
Chlorine production
Specific Application Supply Chain Stage
Components Involved
diaphragm, vent, piping
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
During routine controls a malfunction was observed at the level of the diaphragm. . The accident occurred when proceeding to a cell ‘vaccination’ procedure, consisting in improving the seal of the orifice plate (diaphragm) separating chlorine and hydrogen. This is achieved by injecting suspended silica and magnesium chloride or glass fibres
Consequences
Number of Injured Persons
2
Number of Fatalities
0
Post-event Summary

Two workers were very lightly injured, both having experienced a shock fro mthe explosion and having skin irritations in the legs caused by the acidic electrolyte (pH=3). The chlorine discharged inside the workshop amounted to between 2 and 3 kg. The series of 132 electrolytic cells in the shop were shut down, followed by the entire production chain.

Event Nature
Emergency Action
The production unit was stopped
Release Type
Release Substance
Cl2 H2
Hydrogen Release Concentration (%)
0.00
Release Amount (kg)
3.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event no. 30637 of the French database ARIA (accessed December 2020)