Explosion on a cold box
An explosion occurred in a nitrogen wash cold box (outside the equipment) after a several day cold shutdown followed by a derime with nitrogen. It is assumed that ice may have split tubes permitting carbon monoxide and hydrogen to leak into the perlite installation. It is likewise assumed that the insulation had channelled and had many voids. However, the insulation was continuously purged with nitrogen and the mechanism of the explosion is still unknown. [Zalosh and Short, 1978]
Event Date
March 14, 1968
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE were cracks in aluminium welds which leaked hydrogen cumulating in the cold box. A CONTRIBUTING FACTOR was the cold weather which could have caused the formation of ice. Since the cold box thermal insulation, consisting of perlite, was purged with nitrogen, it is unclear why hydrogen and CO could form an explosive atmosphere. The ROOT CAUSE is not provided. It could nevertheless plausibly attributed to design and/or manufacturing (welding) error.