Explosion on a cold box (663)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion on a cold box

An explosion occurred in a nitrogen wash cold box (outside the equipment) after a several day cold shutdown followed by a derime with nitrogen. It is assumed that ice may have split tubes permitting carbon monoxide and hydrogen to leak into the perlite installation. It is likewise assumed that the insulation had channelled and had many voids. However, the insulation was continuously purged with nitrogen and the mechanism of the explosion is still unknown. [Zalosh and Short, 1978]

Event Date
March 14, 1968
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE were cracks in aluminium welds which leaked hydrogen cumulating in the cold box. A CONTRIBUTING FACTOR was the cold weather which could have caused the formation of ice. Since the cold box thermal insulation, consisting of perlite, was purged with nitrogen, it is unclear why hydrogen and CO could form an explosive atmosphere. The ROOT CAUSE is not provided. It could nevertheless plausibly attributed to design and/or manufacturing (welding) error.

Facility Information
Application Type
Application
cryogenic separation of H2 feed gas
Specific Application Supply Chain Stage
Components Involved

cold box

Storage/Process Medium
Location Type
Location description

DECRITION OF THE PROCESS A "derime" is a maintenance procedure used to remove frozen impurities from a cryogenic system, such as a nitrogen or air separation unit. This is done by warming up the equipment and flowing a warm, dry gas through it to melt and purge any accumulated moisture, carbon dioxide, or other contaminants that would otherwise freeze and block the system. The terms "derime," "defrost," "de-ice," and "thaw" are often used interchangeably for this process.

Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

1900000

Event Nature
Release Type
Release Substance
H2 CO
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Event description extracted from the UK database ICHEME in PDF. The ICHEME database is no longer available for purchase, but data can be download as PDF for free. https://www. icheme. org/knowledge/safety-centre/resources/accident-data/(accessed October 2020)

Table III of Appendix A of Zalosh and Short COMPARATIVE ANALYSIS OF HYDROGEN FIRE AND EXPLOSION INCIDENTS Quarterly Report No. 2 for Period December 1, 1977 - February 28, 1978 https://www. osti. gov/biblio/6566131 (accessed September 2020)

The primary source was in the journal Loss of Prevention (vol. 3), not available anymore