Skip to main content

Explosion in a chemicals plant (1209)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a chemicals plant

An explosion occurred in a plant producing organic chemistry products, in an autoclave located near a distillation column for acetone and oxygenated solvents. The explosion was followed by a fire involving the facility. Internal and external firefighters were mobilised. Site activity was stopped and personnel evacuated. The fire was brought under control in few minutes, by means of fixed installation water hoses and water curtains to protect neighbouring facilities. The whole emergency lasted approximately 1 hour. During a general maintenance shutdown the previous month, the operator had repaired a valve belonging to the hydrogen network and located upstream of the autoclave. It is assumed that a residual leak through the repaired valve or a handling error made during the maintenance operation caused the presence of hydrogen in the autoclave. The activities aiming at restarting the autoclave had just begun, and during flushing of the autoclave, the hydrogen escaped through the vent and ignited upon contact with air, causing a deflagration outside the equipment. An observer noted the orange colour of the flame, which could be due to the presence of organic residues in the autoclave.

Event Date
October 11, 2024
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the accidental release of hydrogen from the autoclave due to the malfunctioning of a valve. The ROOT CAUSE could be attributed to the lack of in-depth risk assessment of the autoclave operation. The procedure of restarting the autoclave was following a fixed series of step, without safety checks. Probably the action of purging the autoclave with nitrogen had been considered safe enough, and further risk analysis deemed unnecessary. Furthermore, the absence of a pressure gauge on the autoclave made it impossible to detect the increased in pressure in the autoclave caused by the leak. The report proposes also the possibility of a human error causing the valve to release hydrogen into the autoclave, but it remains a hypothesis.

Facility Information
Application Type
Application
Basic chemicals products
Specific Application Supply Chain Stage
Components Involved

valve, autoclave

Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary

The autoclave operatios were restarting after the reair of a hydrogen feed line.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Post-event Summary

No personal injury, no property damage reported. Probably the damage was very limited. The palnt restarte operations one week later.

Event Nature
Emergency Action

Detailed timeline of the event: 7:50 - explosion at the autoclave, followed by a fire. 7:50 - 8:00 The operator brought the fire under control in few minutes the fire-fighting action using facility's fixed resources, consisting of a water curtain and water hose. The internal firefighters brigade was mobilised, and the external emergency service called. 8:00 The operator triggered the plant emergency plan and evacuated the personnel. The distillation column was inerted by injecting nitrogen. The extinguishing water was collected. 8:15 External emergency services arrived on site but did not need to intervene. Thermal, toxicological, and explosimetric camera measurements revealed no anomalies in the initial fire zone. 8:53 The emergency plan was lifted Production restarted the following week after safety checks were implemented.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Prefet de la Savoie, Rapport de l'Inspection des installations classées - Visite d'inspection du 22/10/2024 Contexte et constats: https://georisques. gouv. fr/webappReport/ws/installations/inspection/1OXcb52ajVRM1KlkSpmnCTRC0kt7r6B0 (accessed September 2025)

Event no. 62875 of the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/27273/ (accessed December 2024)