European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre
Explosion from a CGH2 tube trailer (475)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Explosion from a CGH2 tube trailer
Two explosions rocked the industrial area of Santa Clara afternoon June 1st 2019, sparking a smoky fire at a chemical, gas storage and transportation facility of Air Products and Chemicals Inc. near the 1500 block of Norman Avenue, Santa Clara, the San Francisco Bay Area, California. No injuries were reported, according to fire officials. The first explosions came just before 4:30 p. m. , Saturday. The blasts were felt five miles away and the area was quickly evacuated as firefighters worked to get the upper hand on this dangerous blaze. A person working across the street from the Air Products plant heard and felt the explosions. He captured images with his cell phone of flames shooting over the fence. According to the Santa Clara Fire Department, a hydrogen trailer CT450 was being fuelled. The tanker truck CT450 started leaking and there was a large hissing noise. When the shutdown of the tanker truck that was being fuelled occurred, an explosion resulted. That is when the initial explosion went off. The explosion damaged the emergency shut off panel and valve near the tanker. At least 4 workers at the Air Products plant were on site during the explosion. Workers were able to shut off two valves but could not shut off the valve near the original tanker truck. According to firefighters those workers were lucky to be alive since they stayed the proper distance away from their truck during the fuelling process. The tanker caught on fire, which spread to other tankers nearby. Only some tankers in the fuelling area were affected and the fire did not spread beyond that area. Nobody was injured. Multiple vehicles were damaged by the explosion and Air Products has temporarily suspended deliveries from its CT-450 and CT-500 fleets while the incident is being investigated. Air Products said in a statement, ” There was significant damage to the distribution trailer directly involved in the incident, as well as to multiple other distribution trailers at the site. ”
The INITIATING CAUSE was a hydrogen leak was caused by either a cracked O-ring or leaking cone and thread fitting on the front module hydrogen isolation valve ROOT CAUSES According to the H2 Safety Panel report, the release of high-pressure hydrogen at the transfer facility has been caused by a miscommunication between the senior driver/trainer and the driver/trainee. The former had disassembled the piping supplying hydrogen to the trailer cylinders trying to repair a leaking valve, without being authorised to do so. The latter actuated the flow to the open pipe section when he inadvertently opened the trailer valves that had an ambiguous control label. A flammable hydrogen-air mixture rapidly formed in and around the trailer front module and an explosion occurred when the mixture was ignited. Because of lack of adequate venting of the open top of the module, a deflagration occurred that subsequently damaged the module and pressured components such as PRDs and high-pressure seals. A domino effect followed triggering the pending of other PRD’s, producing jet fires directed to trailer cab and the adjacent trailers, diesel fuel fires and tire fires.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.