Explosion and fire in a metal hydride storage production plant
An explosion and fire occurred at around at a company specialised in hydrogen storage in slid materials. The accident occurred while a press used to compact magnesium hydride and natural graphite into pellets was being reassembled following maintenance. The manufacturing of the pellets created dust inside the vacuum chamber. This dust built up on various areas of the press (bellows, front and rear of the press, valve, stripper, inside of the airlock and dispenser). To prevent excess powder build-up, the press was cleaned three times a day at the end of each shift. The explosion occurred after the press had been cleaned and when the employees had placed the pressing cavity under vacuum before the injection of argon. Three employees were injured; one suffered slight burns and the two others has ruptured eardrums. The employees extinguished the flames in the casing of the vacuum pump and the press airlock before the fire-fighters arrived. Property damage was primarily limited to objects immediately adjacent to the press but the pellet production line was shut down for several months. The decision to build an extension to the shop was pushed back. The report issued by one of the specialist firms postulated an explosion of the magnesium hydride and/or hydrogen dust inside the pelleting chamber containment. Hydrogen may have been desorbed at ambient temperature from the magnesium hydride powder. Moisture in the air can produce this phenomenon (according to MgH2 + H2O → 3H + MgOH ). A failure of the vacuum system after the doors of the press were closed may have caused the powder mixture to become suspended and form a confined cloud that spontaneously ignited in contact with air. The firm recommended conducting a variety of tests to establish the characteristics of the powder mixture (stability, etc. ) and substantiate/disprove the assumptions made.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause is suspected to be the desorption of hydrogen from the magnesium hydride (MgH2) which caused an explosion due to the failure of the vacuum system. The root cause is the complete lack of sound safety procedures, and the failing to learn from the experience of past accidents.