Explosion (192)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion

An explosion without fire or gas emission occurred in the washer of the catalyst activation unit. The unit was stopped for maintenance : 3 external employees were checking the washer. The explosion occurs just after the opening of the manhole on the washer. The employee looking through the hole at this moment was seriously injured.
Event Date
April 25, 2001
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
One of the possible cause of the explosion could have been to the presence of hydrogen in the washer. Another cause, considered more probable by the ARIA report (see references) could be a secondary reaction or a reaction activation which was still running in the washer.
Facility Information
Application Type
Application
Inorganic chemicals products
Specific Application Supply Chain Stage
Components Involved
washer, catalyst activation unit, Production of hexamethylenediamine
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE PROCESS The catalyst was produced with a mixture of aluminium and nickel which reacts with soda to produce Raney nickel and hydrogen. Hydrogen is evacuated by the ventilation and the Raney nickel is transferred in the washer.
Operational Condition
Consequences
Number of Injured Persons
3
Number of Fatalities
0
Post-event Summary

Prevention plans will be improved. The water seal of the washer is separated from the rest of the unit to avoid hydrogen entry. Evacuation plan will be improved.

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description no 20274 in the French database ARIA.