Skip to main content

Continuous release in open atmosphere (639)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Continuous release in open atmosphere

An operator on patrol discovered a flame coming from the heat exchanger flange of a gasoline hydrodesulphurisation plant and reported it. The plant was immediately shut down. An investigation revealed that the bolts on the flange were not properly tightened, causing the release of gasoline and hydrogen and their ignition.
Event Date
August 3, 1981
Record Quality Indicator
Region / Country
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was loss of tightness of a flange due to loose bolts The ROOT CAUSE could be attributed to incorrect tightening of the bolts during installation, which was not able to compensate for the differential thermal expansion of bolts and flange.

Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
Flange, heat exchanger
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Release Type
Release Substance
H2 gasoline
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): https://www. khk. or. jp/public_information/incident_investigation/hpg_incident/incident_db. html (accessed May 2025)

The first entry in HIAD was coming from RISCAD, which is now closed.