Collision and fire from a CGH2 trailer
A CGH2 tube trailer-tractor was hit at the rear by another vehicle, an empty flatbed trailer-tractor. Because of the collision, at least two tube safety valves were broken. The released hydrogen ignited and the fire engulfed the other eight cylinders, which over-heat, causing the pressure relief valve to activate and release the whole content (350 kg).
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the damage to the pressure control system caused by the collision caused by another vehicle. The safety measures operated as expected. The ROOT CAUSE is difficult to determine. A better design could guarantee stronger protection of the trailer pressure control system, and therefore the reduction of the probability of an escalation. However, it is difficult to take into account all possible crash scenarios generated by traffic.