CHH2 tube trailer internal explosion
An explosion occurred at a the compressed gas storage facility of a research laboratory, during filling hydrogen cylinders from a hydrogen tube trailer. Workers used a manifold containing residual oxygen, which was also connected to a tube trailer of oxygen. There was only one valve separating the two gases. When attempting to purge oxygen from the manifold using low-pressure hydrogen, the hydrogen-oxygen mixture ignited. The following fire damaged the valve, allowing high-pressure oxygen to flow into the hydrogen tubes of the trailer. The subsequent large mix of oxygen and hydrogen exploded, rupturing some of the tubes and creating a fireball of short duration. The consequence were two injuries and extensive damage to equipment.

The INITATING CAUSE was the failure of the shut-off valve, which allowed oxygen flowing into the hydrogen tube. The IGNITION SOURCE was probably rushing sand particles in the tubing producing sparks. Investigators determined that the fittings for the hydrogen and oxygen delivery systems were similar, allowing the connection of incompatible gases to the same manifold. In addition, workers were not following procedures and did not understand the serious hazards of mixing hydrogen and oxygen. Therefore, ROOT CAUSES were design and installation errors, and a lack of safety standards, training and risk management.