LNG storage, plumbing, and other systems can’t be directly retrofitted to handle hydrogen. The LNG components and systems will need to be removed and replaced with equipment specifically designed for hydrogen. If the concept is to convert existing equipment or an existing ship, then it’s probably impossible. If it’s to convert an existing LNG design on paper, then it’s probably impractical.…

Category: Miscellaneous

It is common to have combustible materials and fuels in a building during construction activities. Commissioning is typically considered part of construction. It is good to see that fire suppression is available. However, given the lack of alarm capabilities, it would seem prudent to have a fire watch posted when hazardous materials are present or being used. Regarding requirements, the…

Category: Miscellaneous

It depends on the service. Variables include disk design, corrosion resistance, number of cycles, and how to close the operating pressure is to the rupture disc set pressure. One approach is to ask the manufacturer for their recommendation. Typical practice for U.S. Department of Transportation vessels and discs is to replace them at the tube requalification (i.e., every 5 to 10 years in the U…

The answer could be no devices at all, just a TPRD, just a PRD, or both. It depends on the potential overpressure scenarios identified during a hazard assessment. TPRDs typically are not used on ASME pressure vessels since they are not ASME compliant devices and since  system siting provides protection from engulfing fires. However, TPRDs are frequently used in portable applications for…

The Panel is not aware of any standard for hydrogen detectors for onboard vehicle applications. Some information is available in the SAE Technical Information Report: TIR J3089 Characterization of On-Board Vehicular Hydrogen Sensors, which was published in 2018.

Category: Detectors

One pertinent reference is a Sandia National Laboratories paper by Schefer et al: Spatial and radiative properties of an open-flame hydrogen plume, Intl J. Hydrogen Energy, 31 (2006): 1332-1340. Information on this and other similar papers are available at https://h2tools.org/bibliography. Further information can probably be obtained from the author of this paper and other papers reporting…

Category: Detectors
Keywords: Detector, Sensor, Flame

There are many manufacturers of multiple  types of flame detectors and it’s best to seek their input for the advantages of different types for specific applications. Regarding flame detector technology, UV detectors have been prone to false alarms from outside sources such as sunlight, lightning, and welding/cutting torches. The newer triple-IR detectors that are specifically designed and…