The SRV orientation is critical for many reasons. Many of these are:
The colors of hydrogen are not different hydrogen molecules. The colors represent the different methods to produce hydrogen. The colors are based on how much carbon is produced into the atmosphere during the manufacture of hydrogen.
That being said there is no difference in hydrogen vent systems design by color, only by the design parameters (i.e. temperature, pressure, flow rate,…
It is normal for some air ingress to occur from the vent stack outlet. This is not a hazard if the stack has been properly designed to withstand an internal explosion or fire. Once hydrogen flow from a device is initiated, it will sweep out any air that might be in the stack. Generally, if the vent rate is insufficient to sweep the air out, then it’s also insufficient to freeze or liquefy air…
The ASME BPV Code, and other Codes by reference, require less than back pressure of 10% of device set pressure from the release flowrate for proper operation of reclosing relief devices such as relief valves. Backpressure from non-reclosing or non-ASME devices may be higher so an analysis is required. It’s not enough to assume the vent system need only be designed for 10% of the set pressure.…
Purging can be accomplished in several ways including by using pressure cycles, sweeping, or vacuum. Sweeping is the least reliable but can be effective on simple pipe runs. In most cases, vent systems are open to the atmosphere and the ingress of air from the outlet is likely. However, the vent system should be designed to handle fire or explosion internally. This
generally is not…
It is not possible to define ignition potential by just velocity without more data (i.e. pressure, materials involved, direction of impact). Due to the multiple methods of developing an ignition source (friction, impact, electrical charge) and the low ignition energy, it is assumed that hydrogen in the air will ignite (between 4 -74%), as it does 30-40% of the time with no known ignition…
Vent stacks and building ventilation systems are different and should be analyzed/designed differently. NFPA 2 has different location requirements for vent stack and ventilation system outlets. There are code requirements for elevation, distances from exposures, and between exposures.
There are no specific regulatory or code requirements for vent system separation distances. These…
The vent system should be designed for the temperature at which it operates (ambient for GH2 and Cryogenic for LH2). The outlet of the vent system should be designed for a fire to ensure the mechanical integrity of the vent system.
The supports should also be designed for these temperatures and the associated expansion and contraction.
It should be ensured that moisture…
Refer to the white paper completed by the HSP for LH2. The same criteria should be applied to
a vent system. See below.
H2Tools Document Library: White_Paper-Qualified_Individuals_for_Liquid_Hydrogen
Similar qualifications for vent system design include:
No, but it depends on the application. Nearly all vents less than 4” in size are not purged with N2. This is primarily due to: 1) large flows required to dilute hydrogen below the flammable range, 2) the cost of the nitrogen, 3) the potential blockage of the stack when being inserted a vent header/stack serving a liquid hydrogen system, 4) the potential for backpressure (depending on the…