The Panel considers two approaches to be acceptable.
The HSP is not familiar with this particular fitting or its potential application in H2 service but can offer engineering judgment. Many similar compression-type swaged fittings are used in H2 service. These fittings must be used within the manufacturer recommendations for pressure, temperature, and fluid service. Deformation is also introduced into stainless steel tubing in other ways, such…
In addition to ANSI/CSA FC1-2014, search for fuel cells in the Hydrogen Fuel Cell Codes & Standards
or H2Tools Bibliography sections.
In the case of fuel-rich mixtures like those in the question, the heat of combustion for the mixture should be calculated on the basis of the oxygen content of the mixture. The heat of combustion per mole oxygen is twice the heat of combustion per mole hydrogen, i.e., it is 286*2 kJ per mole O2. You should be able to do the calculations based on this reply.
This is a complex and sometimes contentious topic. The International Code Council (ICC) addresses hydrogen piping in the …
Example safety guidelines are listed below but may not be all-inclusive (e.g., they do not cover general practices such as lockout/tagout, management of change, job safety analysis), and most are the same as for gaseous hydrogen. Also reference NFPA 2 and CGA documents such as H-3, H-5, and H-7. Additional safety training material can also be found on the following link to courses and…
This is not an easy question since many factors influence how much hydrogen can be transferred from one vessel at a higher pressure to another one at a lower pressure and the rate at which it can be transferred. The pressure in the higher vessel will fall while that in the lower vessel will rise as gas is transferred, so the flow rate will typically slow down and eventually stop as the…
It varies slightly due to different density of LH2 at different temperatures, but a gallon of LH2 at atmospheric pressure (0 psig) is ~113 SCF of H2. The expansion ratio is about 840:1. In metric units, a liter of LH2 at atmospheric pressure (0 MPa) would expand to about 840 liters of STP of gaseous pressure.
The National Fire Protection Association (NFPA), the Compressed Gas Association (CGA), and the Society of Fire Protection Engineers (SFPE) represent the U.S. fire protection and engineering community, and these organizations publish handbooks and standards/guidelines that describe the properties of hydrogen. There are many other organizations and documents that provide similar…