It is difficult to provide trustworthy answers to these questions without understanding the design and configuration of the specific installation. It may be best to consult with a pressure systems expert to evaluate the specific installation and uses. The gas provider may also be a good resource for specifics on gas equipment use. Other beneficial resources include the…
Assuming this question relates to the roof of the enclosure, there are no design criteria on this topic to the Panel’s knowledge. The key to the design would be ensure that the exhaust ventilation inlet is located at the highest point and that there are no pockets that can capture hydrogen (restrict flow to the exhaust inlet).
Information on Toyota’s repair garage approach is available…
It is always recommended that the area in which this work would be done be adequately ventilated and in accordance with the Building Code, NFPA 2 and NFPA 45 if applicable. In the Panel’s opinion, it’s recommended that the weight measuring equipment as you’ve described it be designed for Class 1, Group B, Division 2. Also consult with the local authority having jurisdiction as to the…
A best practice, even for small hydrogen vents, is to vent to a dedicated vent system outside the building where possible. Several international codes and standards can be used to provide guidance; the Panel recommends discussing the configuration with a local fire official to ensure their required standards are followed. In the U.S. NFPA 2, Hydrogen Technologies Code, has information in…
The Panel considers two approaches to be acceptable.
The HSP is not familiar with this particular fitting or its potential application in H2 service but can offer engineering judgment. Many similar compression-type swaged fittings are used in H2 service. These fittings must be used within the manufacturer recommendations for pressure, temperature, and fluid service. Deformation is also introduced into stainless steel tubing in other ways, such…
Agree that it's somewhat surprising that there isn't more research on flame impingement barriers. The Fire Codes are focused on fire resistance ratings, as opposed to impingement. Whereas these are important for building protection, and they offer some basis for reference, they don't necessarily address impingement issues which can be important and more pertinent for…
This is a complex and sometimes contentious topic. The International Code Council (ICC) addresses hydrogen piping in the …
While HSP members have limited experience with MFCs in experimental setups, the Panel does not consider them to be reliable to provide a positive flow shutoff. For safety, a shutoff valve in series is recommended. Projects will also need to consider hazardous electrical rating and location when flowing H2. Regarding Coriolis mass flow measuring devices, Coriolis flow meters measure mass rate…
These distances are based primarily on hydrogen piping releases and resultant vapor clouds and jet flames based on pipe diameter and pressure. It’s important to note that many facilities have issues such as confinement and congestion, so it may be applicable to apply contemporary engineering models to assess risk.