Small leak from a CGH2 trailer
When a CGH2 tube trailer was backing into the terminal stall and getting ready to unhook the tractor a leak was detected on one of the cylinders. It was reported immediately to owner of the trailer and is responsible for its maintenance. When the company expert arrived at the site, they found the top tube was leaking. With soap solution they identified the location of the leak on the valve to rupture disc adapter fitting (piping). The trailer had been inspected by drivers and an instructor before departing from the loading terminal, verifying pressures. During the trip to the delivery site, the drivers had conducted several inspections to ensure correct and stable pressures. No leaks were detected during those inspections. It can be concluded the condition for the leak established during the travel, and that the leak had slowly developed until the moment it could be finally detected by inspection.

The INITIATING CAUSE was probably the loosening of a threaded connection of a valve, probably due to road travel vibrations. The ROOT CAUSE is not provided, however, an effective design should be able to take into account road vibrations on a road vehicle.