Release from hydrogen cylinders storage of a chemical plant
A leak occurred on a rack containing 12 cylinders of hydrogen (50 l at 200 bar each) delivered by a lorry inside the fenced storage area of a bulb manufacturing plant. The plant’s safety manager closed access to the area, had the other lorry drivers on the site cut off their ignitions, and made them evacuate. The firefighters tested the air with an explosimeter and stopped the leak by closing the gate valve located on the outside of the rack. The valve was used to transfer hydrogen from the cylinders to their points of use. The rack had been delivered by a crane lorry. Each of the top four corners of the rack was fitted with a steel ring that was used to lift the rack off the lorry. The gate valve was opened when one of the four lifting chains used to lift the rack off the lorry accidentally wrapped around it.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING cause was the accidental opening of the main hydrogen valve during unloading of the lorry.