Release from hydrogen cylinders storage of a chemical plant (930)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release from hydrogen cylinders storage of a chemical plant

A leak occurred on a rack containing 12 cylinders of hydrogen (50 l at 200 bar each) delivered by a lorry inside the fenced storage area of a bulb manufacturing plant. The plant’s safety manager closed access to the area, had the other lorry drivers on the site cut off their ignitions, and made them evacuate. The firefighters tested the air with an explosimeter and stopped the leak by closing the gate valve located on the outside of the rack. The valve was used to transfer hydrogen from the cylinders to their points of use. The rack had been delivered by a crane lorry. Each of the top four corners of the rack was fitted with a steel ring that was used to lift the rack off the lorry. The gate valve was opened when one of the four lifting chains used to lift the rack off the lorry accidentally wrapped around it.
Event Date
September 9, 2013
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING cause was the accidental opening of the main hydrogen valve during unloading of the lorry.
Facility Information
Application
CGH2 cylinders truck
Specific Application Supply Chain Stage
Components Involved
cylinders
Storage/Process Medium
Storage/Process Quantity
9
Actual Pressure
20
Design Pressure
20
Location Type
Operational Condition
Pre-event Summary
The lorry had been delivered to destination and the unloading of the rack of hydrogen cylinders was ongoing by means of the lorry crane
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

The ARIA report (see references) does not provide quantitative assessment of the amount of hydrogen released.

Event Nature
Emergency Action
13:30 Hydrogen release started - The plant’s safety manager closed access to the area, had the other lorry drivers on the site cut off their ignitions, and commanded an evacuation. The firefighters tested the air with an explosimeter and stopped the leak by closing the gate valve. 15:00 The firefighters left and the plant resumed normal operations.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Release Pressure (bar)
200.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/44315/ (accessed September 2020)