Release during CGH2 transfer
A CGH2 tube trailer was parked at a gas shipping site and was transferring gaseous hydrogen to a stationary storage system. The transfer hose failed releasing hydrogen, which ignited. The resulting fire melted the valves and rupture discs on all tubes. The emergency action plan was initiated, an immediate evacuation of the area was executed and local fire department notified. The fire was extinguished and evacuation over after several hours.
Event Date
October 16, 1989
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the rupture of the flexible hose. The ROOT CAUSE is unknown; it is unclear if the fire affected pressure control systems of the stationary storage system or of the trailer. If the latter is true (which appears very plausible), a possible ROOT CAUSE could be a ill safety design which did not consider the possibility of fire engulfment of critical safety components and did not foresee the need to protect them.