Release from the dispenser of a refuelling station
The vent occurred at a hydrogen refuelling station (HRS) of a research laboratory (not public) serving heavy- and light-duty vehicle. The affected dispenser was a 700-bar dispenser for light-duty use supplied by an on-site gaseous storage of approx. 600 kg. The leak occurred due O-ring extrusion and/or failure, on a medium-pressure manual isolation ball valve (normally open). The valve was connected to the end plug of a medium pressure tank. The failure of an O-ring created an external leak which could not be isolated. The released quantity were small, in the 1 to 2 kg range. The leak was audible, but the hydrogen did not ignite and activated a safety sensor. This leak occurred during the recommissioning of the medium pressure system following extended downtime and rebuild of a system that had been originally installed at a different facility.
Event Date
December 20, 2021
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the failure of a O-ring. The ROOT CAUSE is related not only to a material failure, but also to the fact that the event occurred at the recommissioning of the medium pressure system, originally installed at a different facility, and after extended downtime. Ageing may have played a role in this case.