Release and ignition of hydrogen during CGH2 transfer (367)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release and ignition of hydrogen during CGH2 transfer

During a gaseous hydrogen trailer filling operation, a burst disc relieved, causing a gas release. The gas flow caused the vent pipe to separate at the flared tube fitting, resulting in a fire. The fire caused three additional tubes in the gas trailer to relieve pressure (through their burst discs) increasing the intensity of the fire. [Ordin, NASA (1974)]

Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the burst disc failure, but no reason was given for this. The pulling away of the tube from under the SAE flared fitting indicated faulty assembly. Causes of faulty assembly include: (1) flare on tube too short (short flare is squeezed, then due to smaller area, tube is loosened), (2) nut too loose, (3) tube end not squarely cut, (4) foreign material in joint when tightened, (5) split flare. This suggests that the ROOT CAUSES were a combination design and installation shortcomings, possibly assisted by not enough specific procedure.

Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved

burst disc

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Mishap no 15 in P. L. Ordin, Review of hydrogen accidents and incidents in NASA operations, 1974, NASA TM X-71565 https://ntrs. nasa. gov/citations/19740020344