Lightning striking the stake of a chemical plant
A lightning strike ignited the hydrogen exiting a stack in a chemical factory. The hydrogen, produced by the chlorine electrolysis cells, was conveyed to the stack when the manufacturing unit using it was shut down. The internal emergency plan was activated. The electrolysis production chain was put into minimal operation mode. Nitrogen and steam were injected into the stack, which was kept cooled by in-house first responders. The situation was brought under control at 40 minutes later. The emergency plan was lifted and chlorine production resumed at its usual pace. Following a previous similar accident (ARIA database number 44133), the plant had set up a preventive procedure in the event of a thunderstorm hazard, including a storm alert subscription and preventive injection of steam into the stack to dilute the hydrogen and increase the energy needed to ignite it. However, the system was not active at this time of year (storms were traditionally rarer during the winter).
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
As the accident had already occurred once before (ARIA database number 44133), a preventive procedure in the event of a thunderstorm hazard had been set up (including a Storm Alert subscription and preventive injection of steam into the stack to dilute the hydrogen and increase the energy needed to ignite it), but the system was not active at this time of year (storms were traditionally rarer during the winter).