Leakage from a valve in a heavy-oil hydro-desulphurisation unit (637)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Leakage from a valve in a heavy-oil hydro-desulphurisation unit

The incident occurred during the start-up after a routine repair of the refinery's heavy oil hydrodesulfurization system. A valve at the inlet pipe of a high-temperature and high-pressure separation tank ruptured, resulting in oil and gas spillage. The valve was part of a pressure gauge instrument. It failed at the welding, due to hydrogen and hydrogen sulphide attack. Its weld material had an excessively hardness due to insufficient heat treatment after welding. This conclusion was based on the findings of the post-incident investigation: (i) The fracture was approximately in the middle of the butt weld between the valve body and the sealing. (ii) On the inner circumference of the fracture surface, a small weld bevel remained, indicating incomplete penetration of the weld. (iii) The hardness at the weld fracture was high. (iv) Both the base metal and the welded metals were normal and in accordance with the specified standards. (v) From a microstructural point of view, both the welded metal and the welding heat-affected zone of the damaged part were showing hardened structures such as those observed at the time of quenching. It points out at an insufficient post-welding heat treatment. There were no signs of decarburization with hydrogen. (vi) Observations by scanning electron microscope revealed a pseudo-sheared fracture surface, characteristic of delayed fracture by hydrogen.
Event Date
May 17, 1984
Record Quality Indicator
Region / Country
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CASUE was the failure of a welding between a pipe and a pressure gauge. The ROOT CAUSE was shortcoming in the manufacturing of the weld.

Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
valve
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary

The unit was restarting after a routine repair.

Consequences
Number of Injured Persons
3
Number of Fatalities
0
Lessons Learned
The incident highlights the complexity and the possible pitfalls of the relationship between suppliers of components and the plant operators. From the point of the valve manufacturer (the supplier), this incident was the results of a manufacturing error, the failure to execute a weld respecting the specification. It could be as well be attributed to lack of quality control. From the point of the user (the plant operator) the incident could be classified as a case of ‘force majeure’, because the user choose the supplier and specified the quality/application standard, but was not able to assess the quality of the weld and the compliances to the standard.
Event Nature
Emergency Action
After the leak, the device was immediately stopped with an emergency preocedure. in two minutes, the decompression operation started and the system wnet down to atmospgeric pressure i n20 minutes, after which purging with nitrogen was started.
Release Type
Release Substance
H2 heavy gas oil
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

JST failures database: https://www. shippai. org/fkd/include/fkd_showCase. php?id=CC0000164&text1=1984-05-17 (accessed Dec 2024)

Picture from the JST Failure Knowledge Database report CC0000164 reporting the location of the leak (google translation)

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): https://www. khk. or. jp/public_information/incident_investigation/hpg_incident/incident_db. html (accessed May 2025)