Leak from a hydrogen compressor
A leak occurred on hydrogen compressor in a plant of production of renewable hydrogen. A pipe on the condensate purge circuit of the compressor ruptured, releasing hydrogen and producing a noise peak detected by the area's ultrasonic leak detector located in the building. 3 minutes later, the fixed hydrogen detectors in the area measured a hydrogen concentration in the air above 10% of the LEL, and the plant automatically went into safety mode. The production unit was shut down, the compressor was isolated, the facilities were depressurised, and forced ventilation remained activated. Approximately half hour later, the detectors were no longer detecting presence of hydrogen in the production area. The next day, the operator replaced the leaking the ruptured pipe and its connection on the compressor's condensate drain circuit and inspected similar equipment, such as other condensate drainpipes on the other compression stages, before restarting operations.

The INITIATING CAUSE was the rupture of a pipe on the compressor. When the drain valves on the condensate circuit of one of the compressor stages were opened as scheduled, hydrogen circulated through the leaking pipe, leading to its release into the premises. The gas tank supplying the compressor (probably a buffer tank between the production unit and the compressor) gradually emptied into the premises, while the other production equipment was isolated when the site was put into safety mode. Since the safety system worked as designed, and nothing is known on the reason for the rupture, its inspection and maintenance schedules, etc. the ROT CAUSE can be attributed to a generic material failure.