Leak from a CGH2 trailer (233)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Leak from a CGH2 trailer

A CGH2 trailer-tractor arrived at a customer’s site for delivery. When stopping at gate and coming out of the cab, the driver noticed a noise coming from the rear of the trailer. The driver opened the rear cabinet door and found a pigtail line cracked. Hydrogen was leaking from the shut-off valve and to a minor extent from the crack. The emergency team on the customer site washed the rear of cabinet until the delivery company expert arrived on the scene. The expert cut and crimped the cracked line. He then placed a block in the valve to secure the leaking tube. The driver did not execute the delivery and returned the full trailer to the home site without incident. The investigation revealed that road vibration had caused the line to the pigtail to crack. The pigtail and valve seat were replaced and the trailer was brought back to service.

Event Date
June 2, 1991
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE were road travel vibrations damaging a pigtail connection in the trailer pressure control cabinet. The ROOT CAUSE was shortcoming in the design, and possibly also in the installation of the pigtail - valve connection.

Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved

pigtail, valve

Storage/Process Medium
Storage/Process Quantity
331
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

52

Property Loss (offsite)

0

Lessons Learned

Simulation studies have shown that a leak inside the trailer control cabinet could cause the formation of a flammable atmosphere. In this case, it is probable that the hydrogen flow of the leak was very small and allowing dispersion in place of formation of a flammable gas mixture. Nevertheless, the cabinet should be handled as an explosive atmosphere zone and preventing/mitigating measures have to be taken into account in its design. Moreover, a procedure should be in place, which allow the driver to understand what is happening in the cabinet without having to open manually the cabinet door, an action which could provide the ignition energy to a hydrogen-air mixture.

Event Nature
Emergency Action

The emergency tem on the customer site washed the rear of cabinet until the delivery company expert arrived on the scene. The expert cut and crimped the cracked line. He then placed a block in the valve to secure the leaking tube.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Incident I-1991060202 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal. phmsa. dot. gov/analytics/saw. dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)