Hydrogen release from a public transport bus
The accident occurred at a production, distribution and storage station for hydrogen city busses. After filling the hydrogen cylinders of a bus, the hydrogen detection system of the bus triggered an alarm. The site technician pushed the emergency button and the station was put in safety mode. The technician in charge of filling disconnected the hydrogen hose that connects the station to the bus. The maintenance manager of the bus manufacturer was alerted and arrived 20 minutes later and evacuated the personnel. They closed the valves of the on-board storage system and removed the bus top bonnet to allow the hydrogen to disperse in the atmosphere as rapidly and effectively as possible. The emergency services (fire brigades) were called. The station was shut down for 24 hours. The bus was taken off the road while the cylinder manufacturer carried out an investigation. Approximately 8 kg of hydrogen, i. e. one cylinder, was released into the atmosphere. [ARIA]
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE of the release was a partially misplaced O-ring of the Pressure Release Device of the tanks. It remained undetected because the leak was extremely small. The ROOT CAUSE of this misplacement or erroneous mounting lies somewhere along the supply chain. Piping and connections are usually delivered by Tier 1 suppliers, the on-board storage system probably by Tier 2 suppliers, or assembled by the bus integrator. Moreover, the actions taken after the alarm revealed deficiencies in the handling of emergencies.