Hydrogen release from a desulphurisation unit in a refinery
The charge pump on a hydro-desulphuriser unit tripped. The charge flow control valve then opened wide on low flow. The high pressure hydrogen supply to the unit flowed backwards through a faulty non-return valve to the charge tank. The tank vents were not designed for this high flow of gas and so the weak roof to the wall seam failed. Fortunately, the gas did not find a source of ignition and so there was no fire. The pump could have failed due to reverse rotation, but did not.
Event Date
January 1, 1976
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was a mechanical equipment failureThe root cause could be perhaps found in design or operation cause (failure of proper maintenance or inspection). The safety design did not take into account this type of event sequence.