Hydrogen relase fro ma metal treatment furnace
The event occurred at a pit furnace for metal component treatments. The hydrogen feed system for the furnace developed a leak, located on the hydrogen dryer inside a shack attached to a building. The leak vented hydrogen at 200 psig (approximately 15 bar) into the shack. The hydrogen low-pressure alarm sounded. No furnace operators were present at the time. An estimated 10,000 standard cubic feet (25 kg) of hydrogen vented. The hydrogen release was caused by a failure of an elastomeric pressure seal on the body of a particulate filter located in the hydrogen supply circuit of the pit furnace. A month earlier the same incident happened and was identified as a simple seal failure. However, an independent engineering review after the present incident showed the cause to be system overpressure, caused by the failure of a regulator.
Event Date
October 11, 1991
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was the damage to a seal, which started leaking. The reason for the damage was the malfunctioning of a pressure regulator, which caused overpressure to the low-pressure part of the hydrogen supply system. The high-pressure part had been revamped and renovated, but the medium-low pressure part was still consisting in the original setting, including the high-to-low pressure interconnecting component. Therefore, the ROOT CAUSE could be identified in shortcoming when re-designing the installation.