Hydrogen relase fro ma metal treatment furnace (125)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen relase fro ma metal treatment furnace

The event occurred at a pit furnace for metal component treatments. The hydrogen feed system for the furnace developed a leak, located on the hydrogen dryer inside a shack attached to a building. The leak vented hydrogen at 200 psig (approximately 15 bar) into the shack. The hydrogen low-pressure alarm sounded. No furnace operators were present at the time. An estimated 10,000 standard cubic feet (25 kg) of hydrogen vented. The hydrogen release was caused by a failure of an elastomeric pressure seal on the body of a particulate filter located in the hydrogen supply circuit of the pit furnace. A month earlier the same incident happened and was identified as a simple seal failure. However, an independent engineering review after the present incident showed the cause to be system overpressure, caused by the failure of a regulator.
Event Date
October 11, 1991
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the damage to a seal, which started leaking. The reason for the damage was the malfunctioning of a pressure regulator, which caused overpressure to the low-pressure part of the hydrogen supply system. The high-pressure part had been revamped and renovated, but the medium-low pressure part was still consisting in the original setting, including the high-to-low pressure interconnecting component. Therefore, the ROOT CAUSE could be identified in shortcoming when re-designing the installation.

Facility Information
Application Type
Application
pit furnace treatment
Specific Application Supply Chain Stage
Components Involved

pit furnace, pressure regulator, gasket

Storage/Process Medium
Actual Pressure
1
Design Pressure
1
Location Type
Operational Condition
Pre-event Summary

Part of the hydrogen supply system had been renewed.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

low

Property Loss (offsite)

0

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Events in database H2TOOLS https://h2tools. org/lessons/hydrogen-furnace-leak (accessed December 2025)