hydrogen leak in the hose of a dispenser
This incident occurred at a 70MPa hydrogen refuelling station. After completing a filling test, the pressure in the filling hose suddenly dropped. A worker heard the hissing sound of a hydrogen release. By using a portable gas leak detector, the worker discovered a hydrogen leak at the filling hose, near the connection to the dispenser. The facility was manually shut down. There were no casualties. The only property damage was the breakage of one filling hose. Details A filling test was being conducted to check the durability of a plastic filling hose. 945 fillings per year were the target, corresponding to the expected number of the annual filling during the first phase of hydrogen mobility development. The goal of the test was to confirm that he hose was able to function for a year without replacement needed. After completing the filling operation, cracks appeared near the dispenser side connection part of the plastic filling hose, causing a leak of the hydrogen retained inside the hose. A 1. 4 mm long crack was on the outer surface of the inner layer, a 2. 5 mm long crack on the inner surface of the inner layer, and a 1. 5 mm x 2. 0 mm through hole in the outer layer. This hose failed after 130 filling cycles.

INITIATING CAUSE was crack in the filling hose. Post-incident investigation showed that the cracks develops as a combination of hydrogen, cold temperature and bending fatigue at the tensile side. The ROOT CAUSE is therefore design-related.